Musse Mohamud Ahmed, Mohammad Kamrul Hasan, Muhammad Shafiq, Md Ohirul Qays · 7 authors
Utilities produce and supply products following local requirements and with the synchronizations which connect subscribers. Harmonics is a power efficiency/quality variable caused by electronic devices that domestic and industrial consumers use. The famous IEEE Standard 519 is maintained to calculate harmonic limits, which ensures power efficiency. In a standard power system, currents and voltages generate pure sine wave signals during regular operations. As harmonics influence the power system, they cause interference in the sine wave signals. So, the best practice method should be used to resolve the harmonics issue. One of the problem-solving techniques of harmonics is the measurement and reduction of harmonics detection, and it uses Fast Fourier Transform (FFT). Therefore, power output should assess in a peer-to-peer Blockchain scheme by measuring and minimizing harmonics detection. This paper uses a Shunt Active Power Filter (SHAPF). It describes the simulation analysis and reduction of harmonics detection in a peer-to-peer interconnected 3-phase power system with the help of an FFT algorithm. This research was carried out to assess the efficiency of the AC signal by collecting, processing, and evaluating power data. Using the shunt active filter, the proposed design outperformed the traditional methods for both six and twelve pulse rectifiers, achieving total harmonic distortion (THD) of only 1.42% and 0.92%, respectively.
This paper presents the actual measured site data obtained from an operational cryptocurrency mining site. A comparative analysis is then presented to demonstrate the consistency between previously reported test data and operational behaviors of cryptocurrency mine sites. The analysis includes simulation results which utilize the previously observed harmonic spectrum to determine expected distortion levels as a consequence of cryptocurrency mining loads. The effects of the cryptocurrency mining loads are then quantified through comparison to standards indicated in IEEE Std. 519.
Keaton A. Wheeler, Anthony W. Bowers, Charlie H. Wong, Jonathan Y. Palmer · 5 authors
This paper conducts a load and power quality analysis on a 3-feeder distribution system with a cryptocurrency mining system connected. The study includes power factor and harmonic distortion analysis of actual measured 15-minute data over three days in conjunction with measurements of startup and steady state waveforms to determine the load profile of a cryptocurrency mine when connecting to the electrical grid. In addition, comments are made on the effect of the substation transformer. In the context of this paper, multiple load levels are investigated through a thorough analysis of a sample test system. The effects of the cyptocurrency mine are then quantified through comparison to standards indicated in IEEE Std. 519.